Feasibility of Resonance in the 400 kV Abu Taleb-Torbat Jam Transmission line
|
Javad Modarresi * , Ebadollah Kamyab  |
|
|
|
Abstract: (2366 Views) |
Resonance in transmission lines can cause unusual over-voltages and put the equipment at risk. One of conditions that can lead to resonance in transmission lines is the asymmetrical connection (single-phase and two-phase) of transmission lines compensated by shunt reactor. The asymmetrical connection of the line can be caused by the failure of the circuit breaker, activation of the single-phase recloser, or the presence of switchsync relay. In this paper, the feasibility of resonance in the 400 kV Abu Talib-Torbat Jam transmission line is investigated using EMTP-RV software. According to the results, in the case of asymmetrical connection (single-phase and two-phase) of the Abu Talib-Torbat Jam transmission line, resonance does not occur in the power frequency. But this line has a resonant frequency in the range of harmonics. In order to investigate the effect of harmonics, harmonic studies have been conducted and it is shown that harmonics cannot cause unusual over-voltages in this line.
|
|
| Keywords: Resonance, Transmission line, Shunt reactor, Asymmetrical connection |
|
|
Full-Text [PDF 9406 kb]
(704 Downloads)
|
Type of Study: Scientific-extension |
Subject:
Special Received: 2023/04/30 | Accepted: 2023/03/20 | Published: 2023/03/20
|
|
|
|
|
|